HHL series of equipment, in order to site lifting convenient, can be split into a number of packaging factory,
shipped to the scene and then assembled;
equipment supporting the annex,instruments, etc. are installed on the equipment, but the scene of the motor wiring,
control power
Cable, connecting the pipeline is not within the scope of supply;
If you want to increase the function on the basis of the standard function of the equipment, please make accurate written
technical requirements as the contract annex when ordering.
electrical control cabinet to be stated: start mode, control the number of pumps, pump power, signal interface, etc. as a
contract annex.
equipment fire work pressure limit; not less than 0.15Mpa
The fire service rating of the equipment shall not be less than 10L / s
The fire rating of the equipment shall not be less than 0.3 Mpa
equipment compensation water volume or effective water volume: not less than 0.3m3