Fire Water Supply Equipment of Xbg

Product Details
Customization: Available
Task: Adjust
Structure: Combination

360° Virtual Tour

Diamond Member Since 2014

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
65
Year of Establishment
1998-09-10
  • Fire Water Supply Equipment of Xbg
  • Fire Water Supply Equipment of Xbg
  • Fire Water Supply Equipment of Xbg
  • Fire Water Supply Equipment of Xbg
Find Similar Products

Basic Info.

Model NO.
LSK
Mathematical Model
Linear
Signal
Continuous
Function
Automatic Control
Series
Control Cabinet of Lskb Series of Life, Fire Frequ
Transport Package
Wood Box
Specification
CE
Trademark
liansheng or OEM
Origin
Shanghai, China
HS Code
84101330
Production Capacity
50000

Product Description


Fire Water Supply Equipment of Xbg
Products Name:Fire Water Supply Equipment

Conditions of Use:

1. Normal job requirements to ensure the formation of the ground, water flows should be able to self-irrigation pumps and equipment cavity inlet pressure less than 0.05MPa.

2. Power 3-phase 4-wire, 380V, 50Hz. Indoor use of 0-40 celsius does not freeze, 90% RH the following non-condensing, non-corrosive gases, non-inflammable and explosive gas.

The main purpose:

1. XBG series applied to direct extraction of municipal water pipe network of water supply for fire, life, fire sharing a water supply equipment, fire fighting water pressure, fire inspection and other occasions have special requirements.

2. Fire frequency characteristics of water supply equipment Products

3. Automatic speed control constant pressure water supply, easy to operate.

4. Water pressure conditions in accordance with the need to adjust the extent appropriate.

5. Can effectively prevent the flow of water in a small run-time caused by high-pressure tube and so on.

6. Can realize low-speed fire pump test data logging capabilities, the impact of small low-speed data logging operation, low noise, small power consumption to cancel seizure frequency required for the rated flow capacity of electric water valve and electronic control box.

7. Variable soft-start impact smaller, start-up of high reliability, even if the starting frequency of failure (failure) was also back-up power-frequency step-down start-up (which can be automatically input). 8. Inverter equipped with a sophisticated detection protection, in peacetime patrol test machine is running can be found in advance so that timely maintenance alarm

Performance parameters:

1. XBG series a total of three species, 182 specifications of its range of performance parameters

2. Rated flow Q = 5 ~ 50L / S rated pressure Mpa = 0.3 ~ 1.6Mpa speed n = 1450, 2900 r / min power P = 5.5 ~ 110kw inhalation diameter Dna = 50 ~ 150mm diameter spit export DNm = 80 ~ 300mm
fault phenomenon failure cause elimination methods
  1.No power supply or one or two phase power supply is needed
Check all phases of power supply and restore power supply

 
  2.Poor contact of ac contactor and burning of coil
Repair or replace contactors

 
can not start 3.
The power switch is not closed, malfunction or damaged

 
Close the switch and replace it if the power indicator does not turn on
  4.
Thermal relay trip or damage

 
Check whether the motor is blocked, find out the reason and eliminate it.Manual reset is replaced if it cannot be started
  Water level is too low
Put water in the sink

 
  The motor burned
Repair or replace the motor

 
  1.Line is loose
Check wiring and tighten connectors

 
  2.Frequency converter malfunction Check the fault content, check the cause according to the frequency converter manual, and restart after reset.Or disconnect the inverter power supply for a few seconds, the inverter fault reset before starting.
The manual is normal 3The frequency converter is damaged Repair or replace
Automatic transmission failure 4.Pressure switch damage Repair or replace
  5The pressure transmitter is damaged Repair or replace
  6.Switch failure Repair or replace
Pump non - suction pressure gauge pointer to beat violently Insufficient water supply for perfusion, air leakage at the connection between pipeline and instrument Check pipeline and bottom valve, refill water diversion. Tighten air leakage

The pump consumes too much power

 

Too much flow, impeller wear

 
Check whether the pump shaft is bent, replace the impeller, close the outlet valve to reduce the flow
Fire Water Supply Equipment of Xbg