LSK series automatic control cabinet is composed of automatic control part, peripheral operation execution mechanism, motor comprehensive protection part and all kinds of sensor devices. It is a kind of economical, safe and easy maintenance automatic water supply device based on power frequency to control the pump motor.
fault phenomenon | failure cause | elimination methods |
1.No power supply or one or two phase power supply is needed | Check all phases of power supply and restore power supply |
|
2.Poor contact of ac contactor and burning of coil | Repair or replace contactors |
|
can not start | 3. The power switch is not closed, malfunction or damaged |
Close the switch and replace it if the power indicator does not turn on |
4. Thermal relay trip or damage |
Check whether the motor is blocked, find out the reason and eliminate it.Manual reset is replaced if it cannot be started | |
Water level is too low | Put water in the sink |
|
The motor burned | Repair or replace the motor |
|
1.Line is loose | Check wiring and tighten connectors |
|
2.Frequency converter malfunction | Check the fault content, check the cause according to the frequency converter manual, and restart after reset.Or disconnect the inverter power supply for a few seconds, the inverter fault reset before starting. | |
The manual is normal | 3The frequency converter is damaged | Repair or replace |
Automatic transmission failure | 4.Pressure switch damage | Repair or replace |
5The pressure transmitter is damaged | Repair or replace | |
6.Switch failure | Repair or replace | |
Pump non - suction pressure gauge pointer to beat violently | Insufficient water supply for perfusion, air leakage at the connection between pipeline and instrument | Check pipeline and bottom valve, refill water diversion. Tighten air leakage |
The pump consumes too much power |
Too much flow, impeller wear |
Check whether the pump shaft is bent, replace the impeller, close the outlet valve to reduce the flow |