Fire Fighting Pump with Fixed Centrifugal Fire Pumps

Product Details
Customization: Available
Main Advantage: Xbd Type Fixed Centrifugal Fire Pumps
Type: Self-Starting Diesel Generator

360° Virtual Tour

Diamond Member Since 2014

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
65
Year of Establishment
1998-09-10
  • Fire Fighting Pump with Fixed Centrifugal Fire Pumps
  • Fire Fighting Pump with Fixed Centrifugal Fire Pumps
  • Fire Fighting Pump with Fixed Centrifugal Fire Pumps
  • Fire Fighting Pump with Fixed Centrifugal Fire Pumps
  • Fire Fighting Pump with Fixed Centrifugal Fire Pumps
  • Fire Fighting Pump with Fixed Centrifugal Fire Pumps
Find Similar Products

Basic Info.

Model NO.
XBD3.5/5G-LV
Installation Method
Portable
Stroke
Four Stroke
Cooling Method
Water Cooling
Output Type
AC Single Phase
Transport Package
Wood Box
Specification
CE
Trademark
Liansheng or OEM
Origin
Shanghai, China
HS Code
84101330
Production Capacity
20000

Product Description


Fire Fighting Pump with Fixed Centrifugal Fire Pumps
Products Name:fire fighting pump with Fixed Centrifugal Fire Pumps

Conditions of Use:

1, XBD series apply to transfer the temperature does not exceed 50 Celsius water

2, similar liquid water for fire water supply and other aspects of the water supply.

Performance parameters:

1, XBD series total of 66 specifications of its range of performance parameters;

2, Rated flow Q = 1.8 ~ 2.5m3 / h;

3, rated pressure Mpa = 0.32 ~ 1.28Mpa;

4, speed n = 1450, 2950 r / min;

5, power P = 5.5 ~ 250kw;

6, Inhalation diameter Dna = 65 ~ 300mm;

7, diameter spit export DNm = 40 ~ 300mm.
fault phenomenon failure cause elimination methods
  1.No power supply or one or two phase power supply is needed
Check all phases of power supply and restore power supply

 
  2.Poor contact of ac contactor and burning of coil
Repair or replace contactors

 
can not start 3.
The power switch is not closed, malfunction or damaged

 
Close the switch and replace it if the power indicator does not turn on
  4.
Thermal relay trip or damage

 
Check whether the motor is blocked, find out the reason and eliminate it.Manual reset is replaced if it cannot be started
  Water level is too low
Put water in the sink

 
  The motor burned
Repair or replace the motor

 
  1.Line is loose
Check wiring and tighten connectors

 
  2.Frequency converter malfunction Check the fault content, check the cause according to the frequency converter manual, and restart after reset.Or disconnect the inverter power supply for a few seconds, the inverter fault reset before starting.
The manual is normal 3The frequency converter is damaged Repair or replace
Automatic transmission failure 4.Pressure switch damage Repair or replace
  5The pressure transmitter is damaged Repair or replace
  6.Switch failure Repair or replace
Pump non - suction pressure gauge pointer to beat violently Insufficient water supply for perfusion, air leakage at the connection between pipeline and instrument Check pipeline and bottom valve, refill water diversion. Tighten air leakage

The pump consumes too much power

 

Too much flow, impeller wear

 
Check whether the pump shaft is bent, replace the impeller, close the outlet valve to reduce the flow
Fire Fighting Pump with Fixed Centrifugal Fire Pumps
Fire Fighting Pump with Fixed Centrifugal Fire Pumps